RYYQ-T

RYYQ36T7Y1BRYYQ28T7Y1BRYYQ22T7Y1B
SystemOutdoor unit module 1RYMQ16T7Y1BRYMQ12T7Y1BRYMQ10T7Y1B
Outdoor unit module 2RYMQ20T7Y1BRYMQ16T7Y1BRYMQ12T7Y1B
Outdoor unit module 3
Cooling capacityNom.kW101.0 (1)78.5 (1)61.5 (1)
Heating capacityNom.kW113.0 (2)87.5 (2)69.0 (2)
Power input – 50HzCoolingNom.kW31.5 (1)22.0 (1)16.3 (1)
HeatingNom.kW29.8 (2)21.9 (2)16.5 (2)
EER3.21 (1)3.57 (1)3.77 (1)
COP3.79 (2)4.00 (2)4.18 (2)
ESEER4.68 (17)
6.02 (18)
5.23 (17)
6.69 (18)
5.58 (17)
7.07 (18)
Capacity rangeHP362822
Maximum number of connectable indoor units64 (3)64 (3)64 (3)
Indoor index connectionMin.450350275
Nom.900700550
Max.1,170910715
DimensionsUnitHeightmm
Widthmm
Depthmm
WeightUnitkg
FanAir flow rateCoolingNom.m³/min
External static pressureMax.Pa
CompressorType
Operation rangeCoolingMax.°CDB
HeatingMin.°CWB
Max.°CWB
Sound power levelCoolingNom.dBA
Sound pressure levelCoolingNom.dBA
RefrigerantType
Piping connectionsLiquidType
ODmm19.119.115.9
GasType
ODmm41.334.928.6
Heat insulationLiquid, gas and equalizing pipeLiquid, gas and equalizing pipeLiquid, gas and equalizing pipe
Total piping lengthSystemActualm1,000 (10)1,000 (10)1,000 (10)
Level differenceOU – IUOutdoor unit in highest positionm90 (10)90 (10)90 (10)
Indoor unit in highest positionm90 (10)90 (10)90 (10)
IU – IUMax.m30 (10)30 (10)30 (10)
Standard AccessoriesItem
Item
Power supplyNameY1Y1Y1
Phase3N~3N~3N~
FrequencyHz505050
VoltageV380-415380-415380-415
NotesCooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0mCooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0mCooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0mHeating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0mHeating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50%Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50%Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50%
RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDBRLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDBRLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.
Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.Maximum allowable voltage range variation between phases is 2%.Maximum allowable voltage range variation between phases is 2%.
Refer to refrigerant pipe selection or installation manualRefer to refrigerant pipe selection or installation manualRefer to refrigerant pipe selection or installation manual
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A andEuropean/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A andEuropean/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and
Short-circuit powerShort-circuit powerShort-circuit power
system impedancesystem impedancesystem impedance
Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionalityThe STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionalityThe STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)
Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)

Địa chỉ: 106 Cách Mạng Tháng Tám, Khuê Trung, Cẩm Lệ, Đà Nẵng
Email: quoctungme@gmail.com
Hotline0905.999.643

0/5 (0 Reviews)

Trả lời

Email của bạn sẽ không được hiển thị công khai. Các trường bắt buộc được đánh dấu *

Tìm cửa hàng
Gọi trực tiếp
Chat ngay
Chat trên Zalo